Page 9 - SISSYpro_FME_visualizations
P. 9
Image shows: FME 32 W and FME 32 C (photos from the test lab)
Technical data:
1. Type of construction: 10. Decoupling:
19“ plug-in card 6U, 20M galvanic isolation of inputs via optocoupler
2. Weight: 11. Switch-on delay:
approx. 600g up to 20sec
3. Climatic conditions: 12. Debounce time:
in accordance with up to 20ms
UNITRO-PSC-Standard
13. Contact Selection:
4. Connection: quiescent / operating current
male multiple connector: 1x 48-pin E
1x 96-pin C 14. Interfaces:
1x MINI USB
5. Function buttons: (for programming using an external PC)
flashing acknowledge button
15. Function:
6. Supply voltages: millisecond resolution and real-time mapping for
depending on the power supply card SISSYpro first-value annunciator system with
24V DC ± 10% programmable signal conditioning for the event
60V DC ± 10% detection with acknowledgment via integrated
110V DC ± 10% front button and remote acknowledgeable by the
220V DC ± 10% headquarters (SISSYpro),
230V AC ± 10% dead-man timer and watchdog for automatic
voltage-adapted reboot,
message transmission to the control center
7. Inputs:
32 binary inputs, signal voltage: 16. Parameterization:
24V DC via integrated MINI USB interface or assumption
60V DC of parameter data sets from the central SISSYpro
200V DC with fail-safe storage in EEPROM
110V DC 17. Leakage distances and clearances:
voltage-adapted
voltage tolerance ±10% in accordance with UNITRO-PSC-Standard
18. EMC, immunity to interference:
8. Time:
millisecond time synchronization UNITRO-PSC-Standard,
immunity higher degrees of severity according to
9. LED-display: the actual generic standards DIN EN 61000
32 light field displays 10 x 32mm
selectable colors (red/green/yel-
low/blue/white) with exchangeable
marking strips, flashing function in ac-
cordance with DIN 19235
subject to change Page 190