Page 7 - SISSYpro_FME_visualizations
P. 7

Photo shows ZFM with EK32 and optional built-in printer
            Technical data:
             1.    Type of construction:                   1.    Transmission:
                   19“ rack mounting, 84M, 3U,                   LON FTT10A two wire (twisted-pair),
                   mounting depth 270mm                          78kbps, max. 2,7km
             2.    Degree of protection:                   2.    Bus connection:
                   IP20                                          isolated transceiver, 500V disconnecting
                                                                 insulation voltage
             3.    Weight:
                   approx. 7kg,                            3.    Group-signal outputs:
                   depending on equipment variant                optional expandable to 256 outputs
             4.    Climatic conditions:                    4.    Interfaces:
                   in accordance with                            1x USB (for programming using an external PC)
                   UNITRO-PSC-Standard                           1x RS485, 2x RS 232 ports (e.g. for printer)
                                                                 1x LON FTX,
             5.    Connection:                                   16x relay outputs change-over max. 125V 0,4A
                   rear mounted edge-socket connector
                   32-pin wrap DIN 41612 mounting form     5.    System features:
                   D, colour-coded connection line               -   DCF77 radio clock or just optional GPS clock to
                   32x 0,25mm²                                       synchronize to 1ms
                                                                 -   or Time synchronization of the SISSYpro
              6.   Supply voltages:
                   24V DC          ± 10%                             control center
                   48-60V DC       ± 10%                         -   logging with date and time in ms resolution
                   110/125V DC     ± 10%                         -   80 characters per message
                   220/240V DC     ± 10%                         -   selectable for quiescent / operating current
                   230V AC         ± 10%                             per message
                   voltage-adapted                               -   plain text logging, entering the full text with
                                                                     PC
              7.   Inputs (plug-in cards):                       -   debounce time on the time scale of
                   EK32:    3U 4M, 16 channels                       milliseconds
                   FME 32:  6U 20M, channels                     -   switch-on delay on the time scale of seconds
                   24V DC                                        -   flutter-signal handling on the time scale of
                   60V DC                                            seconds
                   110V DC
                   220V DC                                 6.    Leakage distances and clearances:
                   voltage-adapted                               in accordance with UNITRO-PSC-Standard
                   voltage tolerance ±10%                  7.    EMC, immunity to interference:
              8.   Resolution / query cycle:                     UNITRO-PSC-Standard,
                   1ms to 10ms,                                  immunity higher degrees of severity according to
                   depending on the configuration                the actual generic standards DIN EN 61000
              9.   Stages of development:
                   from 16 to max. 512 messages

                                                      subject to change                                Page 188
   2   3   4   5   6   7   8   9   10   11   12