Page 7 - SISSYpro_FME_visualizations
P. 7
Photo shows ZFM with EK32 and optional built-in printer
Technical data:
1. Type of construction: 1. Transmission:
19“ rack mounting, 84M, 3U, LON FTT10A two wire (twisted-pair),
mounting depth 270mm 78kbps, max. 2,7km
2. Degree of protection: 2. Bus connection:
IP20 isolated transceiver, 500V disconnecting
insulation voltage
3. Weight:
approx. 7kg, 3. Group-signal outputs:
depending on equipment variant optional expandable to 256 outputs
4. Climatic conditions: 4. Interfaces:
in accordance with 1x USB (for programming using an external PC)
UNITRO-PSC-Standard 1x RS485, 2x RS 232 ports (e.g. for printer)
1x LON FTX,
5. Connection: 16x relay outputs change-over max. 125V 0,4A
rear mounted edge-socket connector
32-pin wrap DIN 41612 mounting form 5. System features:
D, colour-coded connection line - DCF77 radio clock or just optional GPS clock to
32x 0,25mm² synchronize to 1ms
- or Time synchronization of the SISSYpro
6. Supply voltages:
24V DC ± 10% control center
48-60V DC ± 10% - logging with date and time in ms resolution
110/125V DC ± 10% - 80 characters per message
220/240V DC ± 10% - selectable for quiescent / operating current
230V AC ± 10% per message
voltage-adapted - plain text logging, entering the full text with
PC
7. Inputs (plug-in cards): - debounce time on the time scale of
EK32: 3U 4M, 16 channels milliseconds
FME 32: 6U 20M, channels - switch-on delay on the time scale of seconds
24V DC - flutter-signal handling on the time scale of
60V DC seconds
110V DC
220V DC 6. Leakage distances and clearances:
voltage-adapted in accordance with UNITRO-PSC-Standard
voltage tolerance ±10% 7. EMC, immunity to interference:
8. Resolution / query cycle: UNITRO-PSC-Standard,
1ms to 10ms, immunity higher degrees of severity according to
depending on the configuration the actual generic standards DIN EN 61000
9. Stages of development:
from 16 to max. 512 messages