Page 8 - SISSYpro_FME_visualizations
P. 8
Fleischmann
STÖRMELDESYSTEME
FME 32 W
19” input card for ChronologicalAlarmSystem
Type designation:
FME32 W
signal logging of 32 binary inputs
(light field displays)
with millisecond resolution and
real-time assignment for SISSYpro
first-value annunciator system
according to ISA-18.1 / DIN 19235
System features:
19“ plug-in card 6U, 20M for ChronologicalAlarmSystem (ZFM)
32 binary inputs with millisecond resolution and real-time mapping for
SISSYpro first-value annunciator system
Parameterization about built-in USB port or remote programming via SISSYpro:
cleartext logging with entering the plaintexts, quiescent / operating current,
debounce time on the time scale of milliseconds, switch-on delay and
flutter-signal handling on the time scale of seconds
32 light field displays 10 x 32mm (selectable colors (red/green/yellow/blue or white)
with exchangeable marking strips flashing function in accordance with ISA-18.1 / DIN 19235,
with acknowledgment via integrated front button and remote acknowledgeable
by the headquarters (SISSYpro)
Time with millisecond time synchronization
Message transmission to the control center
Assumption of parameter data sets from the Central SISSYpro
with fail-safe storage in EEPROM
Dead-man timer and watchdog for automatic reboot
EMC-values: Higher immunity levels to UNITRO-PSC-Standard