Technical data:

              1.   Type of construction:                    10.   Decoupling:
                   19“ plug-in card 6U, 20M                       galvanic isolation of inputs via optocoupler

             2.    Weight:                                   11.   Switch-on delay:
                   approx. 600g                                   up to 20sec
             3.    Climatic conditions:                      12.   Debounce time:
                   in accordance with                             up to 20ms
                   UNITRO-PSC-Standard
                                                             13.   Contact Selection:
             4.    Connection:                                    quiescent / operating current
                   male multiple connector:   1x 48-pin E    14.   Interfaces:
                                            1x 96-pin C
                                                                  1x RS232
             5.    Function buttons:                         15.   Function:
                   flashing acknowledge button
                                                                  millisecond resolution and real-time mapping for
             6.    Supply voltages:                               SISSYpro first-value annunciator system with
                   depending on the power supply card             programmable signal conditioning for the event
                   24V DC    ± 10%                                detection with acknowledgment via integrated
                   60V DC    ± 10%                                front button and remote acknowledgeable by the
                   110V DC  ± 10%                                 headquarters (SISSYpro),
                   220V DC  ± 10%                                 dead-man timer and watchdog for automatic
                   230V AC  ± 10%                                 reboot,
                   voltage-adapted                                message transmission to the control center
             7.    Inputs:                                   16.   Parameterization:
                   32 binary inputs, signal voltage:              via RS232 interface
                   24V DC                                         with fail-safe storage in EEPROM
                   60V DC
                   200V DC                                   17.   Leakage distances and clearances:
                                                                  in accordance with UNITRO-PSC-Standard
                   110V DC
                   voltage-adapted                           18.   EMC, immunity to interference:
                   voltage tolerance ±10%                         UNITRO-PSC-Standard,
                                                                  immunity higher degrees of severity according to
             8.    Time:                                          the actual generic standards DIN EN 61000
                   millisecond time synchronization
             9.    LED-display:
                   32 LED with exchangeable marking strips
                   flashing function in accordance with
                   DIN 19235