LVE - MVE-series digital In- Output modules for distributor installation Digital IN module MVE 8/0, 16/0 (i) (H): replaced by LVE 8/0, 16/0 old MVE data sheet with wide-range power supply 85-265V AC / 85-250V DC or 24V AC/DC, Inputs: 24V ((i)=internal supply) and/or (H) with emergency switches 100 x 75 x 45 (85)mm high Digital IN/OUT module MVE 8/8, 8/3w (i) (H): replaced by LVE 8/8 old MVE data sheet with wide-range power supply 85-265V AC / 85-250V DC or 24V AC/DC, Inputs: 24V ((i)=internal supply) Outputs: relay max. 250V AC, 5A normally open or (w) change-over and/or (H) with emergency switches 100 x 75 x 45 (85)mm high Digital OUT module MVE 0/8, /16, /3w, /6w, 3w8s(H): replaced by LVE 0/8, 0/16 old MVE data sheet with wide-range power supply 85-265V AC / 85-250V DC or 24V AC/DC, Outputs: relay max. 250V AC, 5A normally open or (w) change-over and/or (H) with emergency switches 100 x 75 x 45 (85)mm high IN/OUT with on-load relay MVE 8/8-L: to the data sheet with wide-range power supply 85-265V AC / 85-250V DC or 24V AC/DC, Inputs: 24V AC/DC or 230V AC, Outputs: relay max. 230V AC, 16A change-over max. inrush current 80A, 20ms with emergency switches 150 x 75 x 60 (85)mm high OUT with on-load relay MVE 0/8-L: to the data sheet with wide-range power supply 85-265V AC / 85-250V DC or 24V AC/DC, Outputs: relay max. 230V AC, 16A change-over max. inrush current 80A, 20ms with emergency switches 150 x 75 x 60 (85)mm high OUT with on-load relay MVE 0/8-E: to the data sheet with wide-range power supply 85-265V AC / 85-250V DC or 24V AC/DC, Outputs: relay max. 230V AC, 16A normally open max. inrush current 120A, 20ms with emergency switches 150 x 75 x 60 (85)mm high RF suppression module ESF: to the data sheet for the attenuation of 8 changeover contacts (to reduce RF interference), Applications: electronic ballasts, energy saving lamps, blinds and roller shutter motors, etc. 106 x 90 x 58mm high MVE-series as PDF