LVE 8/0, 16/0, 8/8, 0/8, 0/16
digital In- Output modules for distributor installation
Type designation:
LVE 8/0, 16/0
modules with 24V AC/DC or 230VAC inputs
LVE 8/8
modules with 24V AC/DC or 230VAC inputs
and relay outputs max. 250V AC, 5A,
normally open
LVE 0/8, 0/16
modules with relay outputs max.250V AC, 5A,
normally open
System features:
- Snap-on housing for distributor installation in snap-on breakers design 170 x 58 x 90 (115)mm (WxHxD)
- Degree of protection IP20
- Wide-range power supply with 85-265V AC / 85-250V DC or 24V AC/DC, 100mA ±10%
- Network, input and output cards internally-positioned and combined
- Screw terminal plug connection max. 2,5mm²
- Software compatible to MVE-series
- Available types:
LVE 8/8 8x IN and 8x OUT (normally open)
LVE 16/0 16x IN
LVE 8/0 8x IN
LVE 0/16 16x OUT (normally open)
LVE0/8 8x OUT (normally open) - EMC-values: UNITRO-Standard in accordance with EN 61000
Technical data:
- Type of construction:
snap-on housing (WxHxD)
107 x 58 x 90 (115)mm
- Degree of protection:
IP20
- Weight:
approx. 300g,
depending on equipment variant
- Climatic conditions:
in accordance with UNITRO-Standard
- Connection:
screw-type terminals/ plug connection max. 2,5mm²
- Function buttons:
reset button
service button
- Supply voltage:
24V AC/DC, 100mA (± 10%),
230V AC/DC (= 85-265V AC, 85-250V DC), 100mA
- Max. fuse:
4A medium slow
- Signal voltage:
24V AC/DC ± 10%, 6mA
230V AC ± 10%, 6mA
- Response delay:
25ms
- Minimum signal duration:
5ms
- LED-display:
operating LED green
service LED yellow:
flashing = device not initialized
continuous light = error
for every input and output each 1x red LED
- Neuron chip:
3150, 10 MHz + 64kB Flash-EEPROM
- Transmission:
LON FTT10A two wire (twisted-pair),
78kbps, max. 2,7km
- Bus connection:
isolated transceiver, 500V disconnecting insulation voltage
- Relay outputs:
isolated normally open: 250V AC, 5A / 25V DC, 5A
disconnecting voltage: 2000Vrmsinductive load (contactors):
mount-in anti-interference capacitors at the coils,
when driving roller shutter / blind motors, etc. by NO, is foran external interlock (up / down) to make! -
Software:
compatible to MVE-series
- Leakage distances and clearances:
in accordance with UNITRO-Standard
- EMC, immunity of interference:
UNITRO-Standard,
in accordance with EN
subject to change