EMC values

EMC values
EMC values

Information on guidelines and standards applied

EU


2004/108/EG


2006/95/EG

Guidelines


EMC guideline (electromagnetic compatibility)


Low voltage directive (LVD)

.


EN 50178:1997


.
.
EN 61010-1:2001



EN 61131-2:2007

Product standards


Equipping power installations with electronic equipment


Safety requirements for electrical equipment for measurement,
control and laboratory equipment.
Part 1: general requirements


Programmable logic controllers.
Part 2: equipment requirements and tests

.


EN 50178:1997


.
EN 61010-1:2001


EN 61131-2:2007

EMC


EMC Part 6-2 generic standards - Immunity for industrial environments


EMC Part 6-4 generic standards - Emission standard for industrial
environments


EMC - requirements 
Electrical equipment for measurement, control and laboratory use

UNITRO PSC-Standard:

Higher immunity levels in:

EN 61000-4-4
EN 61000-4-5
EN 61000-4-2

severity 4
class 5
severity 4

UNITRO Standard:

Immunity levels to:

EN 61000-4-4
EN 61000-4-5
EN 61000-4-2

severity 3
class 3
severity 3

For the processing of non-independent resources (components) of the applicable regulations are complied with.
When installed in equipment shall also determine the particular device. Standards at the time of printing.

Safety and environmental requirements for EN 50178

-

Climatic conditions:

PSC-Standard

Class 4K4H
Ambient and
operating temperature: -20° to +55°C 
4% to 100% relative humidity

Class 1K4
Storage temperature: -25° to +55°C

Class 2K3
Transport temperature: -25° to +70°C

Standard

Class 3K3
Ambient and
operating temperature: +5° to +40°CC
5% to 85% relative humidity

Class 1K4
Storage temperature: -25° to +55°C

Class 2K3
Transport temperature: -25° to +70°C

Minimum creepage distances:

Degree of pollution 2
250Vrms, 1mm

Degree of pollution 2
250Vrms, 1mm

Insulation test:

325V: 1,1KVrms

325V: 1,1KVrms