EMC values


Information on guidelines and standards applied
EU
2004/108/EG
2006/95/EG
Guidelines
EMC guideline (electromagnetic compatibility)
Low voltage directive (LVD)
.
EN 50178:1997
EN 61010-1:2010+A1:2019
+ A1:2019/AC:2019;
revision 2
EN 61131-2:2007
Product standards
Equipping power installations with electronic equipment
Safety requirements for electrical equipment for measurement,
control and laboratory equipment.
Part 1: general requirements
Programmable logic controllers.
Part 2: equipment requirements and tests
.
EN IEC 61000-6-2:2019
.
EN IEC 61000-6-4:2019
EN IEC 61326-1:2021
EMC
EMC Part 6-2 generic standards - Immunity for industrial environments
EMC Part 6-4 generic standards - Emission standard for industrial
environments
EMC - requirements
Electrical equipment for measurement, control and laboratory use
UNITRO PSC-Standard:
Higher immunity levels in:
EN 61000-4-4:2012
EN 61000-4-5:2014+ A1:2017; revision 1
EN 61000-4-2:2009
severity 4
class 5
severity 4
UNITRO Standard:
Immunity levels to:
EN 61000-4-4:2012
EN 61000-4-5:2014+ A1:2017; revision 1
EN 61000-4-2:2009
severity 3
class 3
severity 3
For the processing of non-independent resources (components) of the applicable regulations are complied with.
When installed in equipment shall also determine the particular device. Standards at the time of printing.
Safety and environmental requirements for EN 50178
-
Climatic conditions:
PSC-Standard
Class 4K4H
Ambient and
operating temperature: -20° to +55°C
4% to 100% relative humidity
Class 1K4
Storage temperature: -25° to +55°C
Class 2K3
Transport temperature: -25° to +70°C
Standard
Class 3K3
Ambient and
operating temperature: +5° to +40°CC
5% to 85% relative humidity
Class 1K4
Storage temperature: -25° to +55°C
Class 2K3
Transport temperature: -25° to +70°C
Minimum creepage distances:
Degree of pollution 2
250Vrms, 1mm
Degree of pollution 2
250Vrms, 1mm
Insulation test:
325V: 1,1KVrms
325V: 1,1KVrms