Type of construction:
Bay: Wall-mounted housing (PS) 233 x 200 x 99,5mm with hinge to
open the front panel (insert the label strips)
Weight approx: 1.500g with rechargeable battery 2.700g
Degree of protection: IP54, terminal box embossment for ports from behind + below
Climatic conditions: 5 to +55°C, 5 to 85% relative humidity
LED-display: 27 RGB LED
Labelling: 3 exchangeable marking strips double spaced inscribable
Function buttons: integrated buttons for test, horn and 2x acknowledge flashing
Integrated horn: Piezo buzzer
Behind separate terminal cover:
Connection: Screw terminal plug connection, max. 1,5mm²
PC connection: USB-B socket
Analogue telephone connection: RJ11 socket
Ethernet: RJ45 socket
Power supply: 230V AC (= 120-250V AC)
Power loss: 15VA
Max. back-up fuse: 10A L
Internal fuse: Picofuse 1,6A slow
Inputs:
Input level for signal inputs: 24V AC/DC 8mA, ± 15%, alternatively internal supplied with 24V
Minimum signal duration: 10ms
Outputs:
Output relays: 5x relay, 1 NO or NC contact, max. 250V 5A
including 1x relay output for horn, max. 250V 5A
Horn acknowledge: Separate connection for acknowledging the horn
Built-in Ethernet port with Web server for visualization
EMC, immunity to interference: UNITRO-Standard in accordance with EN 61000
Option UPS:
Rechargeable battery: Gas-proof, lead- gel rechargeable battery 24V 1,2 Ah
Buffer time 100% ED: 3h
Buffer time signal standby: 10h
Connection for external battery: max. 2,2Ah
Option Tele:
Analog telephone modem for 28 voice messages (Text to Speech)
Option LON- bus:
FTT 10 2-wire output for parallel tableau and GLT connection
Configuration menu / Network configuration:
Parameter setting via USB port or Ethernet port (FTP) from Windows 7 Pro, the following parameters:
Message as a fault or run signal (display only) Message relevant or not relevant
Message with horn, -horn without or with an Quiescent current or operating current
automatic acknowledgment message
Acknowledgeable new value message Response delay variable for each signal
with 1 or 2 flash rates from 1-254sec
24 messages (voice) every 17sec be digitally stored 4 relay contacts, NO or NC contact,
4 Battery status messages: battery operation, inputs freely assignable to outputs
-defect, -low voltage and power recovery
Message texts via TTS (Text To Speech) Automatic cut-off horn max. 254sec
Acknowledgment by front buttons on the unit, Assignment of the 28 message texts
or telephone acknowledgement via acknowledg- on 6 connecting sections
ment code each with 4 numbers
In case of non-acceptance or failure to
acknowledge the message forwarding Basically with start text for each message,
and 7 text modules (acknowledge text)
announcement within 4 to play the numbers dialed
LED colors available: red, green, yellow, blue Delay of phone messages up to
Ethernet network and FTP configuration max. 60 min