                                                                                 STÖRMELDESYSTEME

                                                    CC24


                     Compact Central Fault Indicating Unit


            Type designation:

            CC24
            central fault indicating unit for
            24 message lines with RGB LED-display,
            two flashing frequencies (ISA-18.1/DIN 19235),
            UPS and telephone dialer




            Controls and displays
              Bright 5mm RGB LED display
              Separate status indicator
              Easily exchangeable label strips
              Integrated mini horn and functional keys
              Built-in Ethernet port with Web server for visualization
            Parameterization
              Built-in USB port and Ethernet port (FTP) for parameterization from Windows 7 Pro
              Operation, fault per message
              Quiescent / operating current, relevant / irrelevant – for each signal
              Response delay variable for each signal from 1s to 254sec
              New value flash warning with 1 or 2 flash rates
              4 relay contacts, NO or NC contact, inputs freely assignable to outputs
            Electrical characteristics
              24 message lines 2-pin 24V AC/DC, 8mA ± 15%, (alternatively internal supplied with 24V)
              Acknowledgeable new value flash warning with 1 or 2 flash rates
                all sequences ISA-18.1-1979 (R2004) and DIN 19235
              Minimum signal duration 10ms
              EMC-values: UNITRO-Standard in accordance with EN 61000
              Outputs:  5x relay, 1 NO or NC contact, max. 250V 5A
                           including 1x relay output for horn, max. 250V 5A
              Separate connection for acknowledging the horn

            Mechanical characteristics
              Wall-mounted housing PS 233 x 200 x 99,5mm with hinge for front panel
              Screw terminal plug connection, max. 1,5mm²
              Extended terminal compartment with embossed for cable glands from behind and below

            Options
              Integrated UPS
              Integrated analog modem for remote alarm via voice (Text to Speech)
              2 wire bus connection (LON-bus)


            © UNITRO-Fleischmann    Gaildorfer Str. 15   D-71522 Backnang   Tel.: +49 (0)7191/141-0   Fax: +49 (0)7191/141-299