Page 11 - C3_series
P. 11

Connection diagram C3 digital 8x IN and 8x OUT
















































            Technical data:
               1.   Type of construction:                        10.   LED-display:
                    snap-on plastic housing (polyamide)                see connection diagram
                    with DIN-rail-bus 22,5 x 99 x 113,5mm
                                                                 11.   Relay outputs:
               2.   Degree of protection:                              normally open: 250V AC, 5A / 25V DC, 5A
                    IP20                                               electrical isolation:   2000Vrms

               3.   Weight:                                              inductive load (contactors):
                    approx. 150g                                       mount-in anti-interference capacitors at the coils,
                                                                       please use external interlock, driving shutter or sun
               4.   Climatic conditions:                               blind motors (up / down)!
                    in accordance with UNITRO-Standard
                                                                 12.   Parameterization:
               5.   Connection:                                        via mini USB-interface on the Bus cou-
                    screw-type terminals/ plug connection              pler, connected with the DIN-rail-bus:
                    max. 2,5mm²                                        e.g. quiescent / operating current,
               6.   Supply voltage:                                    delay time, etc.
                    via DIN-rail-bus                             13.   Leakage distances and clearances:

               7.   Signal voltage:                                    in accordance with UNITRO-Standard
                    24V DC ± 10%, 5mA per input                  14.   EMC, immunity of interference:
               8.   Response delay:                                    UNITRO-Standard,
                    25ms                                               in accordance with EN 61000
               9.   Minimum signal duration:
                    5ms