ChronologicalAlarmSystem (ZFM 2378)
Stand-alone or SISSYpro substation
Construction / components
- For maximum 224 messages: installation 19 "rack system 3x 6U (depth 270mm) for:
1x power supply card 3U 6M with power outage notification,
1x CPU 2378, 6U 4M and
7x input cards FME 32 W, 32 per message, 6U 20M
(24V DC / 60V DC / 110V DC / 220V DC labeled with 10 x 32mm light field displays) - For maximum 512 messages: installation 19 "rack system 1x 6U (depth 270mm) for:
1x power supply card 3U 6M with power outage notification,
1x CPU 2378, 6U 4M and
16x input cards EK32, 32 per message, 3U 4M
(24V DC / 60V DC / 110V DC / 220V DC with LED display)
Interfaces / Ports
- On the CPU:
1x USB (for parameterization using an external PC)
1x RS 485 2x RS 232 (e.g. for printer)
1x LON FTX
16x relay outputs change-over max. 125V 0.4A - Connection: rear mounted edge-socket connector 32-pin wrap DIN 41612 mounting form D,
colour-coded connection line 32x 0,25mm² - DCF77 radio clock or just optional GPS Clock to synchronize to 1ms
Parameterization
- via integrated USB interface or remote parameterization by SISSYpro:
cleartext logging with entering the plaintexts, quiescent / operating current, debounce time on the time scale of milliseconds, switch-on delay and flutter-signal handling on the time scale of seconds
Characteristics
- CPU 2378 processor card with time logical message storage
- Time synchronization of the SISSYpro control center or via built-in GPS / DCF clock
- Logging with date and time in ms resolution with 80 characters per message
- EMC-values: Higher immunity levels to UNITRO-PSC-Standard
Options
- Built-in printer
Technical data:
- Type of construction:
19“ rack mounting, 84M, 3U,
mounting depth 270mm
- Degree of protection:
IP20
- Weight:
approx. 7kg,
depending on equipment variant
- Climatic conditions:
in accordance with UNITRO-PSC-Standard
- Connection:
rear mounted edge-socket connector 32-pin wrap
DIN 41612 mounting form D,
colour-coded connection line 32x 0,25mm²
- Supply voltages:
24V DC ± 10%
48-60V DC ± 10%
110/125V DC ± 10%
220/240V DC ± 10%
230V AC ± 10%
voltage-adapted
- Inputs (plug-in cards):
EK32: 3U 4M, 16 channels
FME 32: 6U 20M, channels
24V DC
60V DC
110V DC
220V DC
voltage-adapted
voltage tolerance ±10%
- Resolution / query cycle:
1ms to 10ms, depending on the configuration
- Stages of development:
from 16 to max. 512 messages
- Transmission:
LON FTT10A two wire (twisted-pair),
78kbps, max. 2,7km
- Bus connection:
isolated transceiver, 500V disconnecting insulation voltage
- Group-signal outputs:
optional expandable to 256 outputs
- Interfaces:
1x USB (for programming using an external PC)
1x RS485, 2x RS 232 ports (e.g. for printer)
1x LON FTX,
16x relay outputs change-over max. 125V 0,4A
- System features:
- DCF77 radio clock or just optional GPS clock to synchronize to 1ms
- or Time synchronization of the SISSYpro control center
- logging with date and time in ms resolution
- 80 characters per message
- selectable for quiescent / operating current per message
- plain text logging, entering the full text with PC
- debounce time on the time scale of milliseconds
- switch-on delay on the time scale of seconds
- flutter-signal handling on the time scale of seconds
- Leakage distances and clearances:
in accordance with UNITRO-PSC-Standard
- EMC, immunity to interference:
UNITRO-PSC-Standard,
immunity higher degrees of severity
according to the actual generic standards DIN EN 61000
subject to change