MVL 8/0, 4/4, 0/8
digital In- and Output modules for distributor installation
Type designation:
MVL 8/0
module with 24V DC, 5 mA inputs
(24V optional internal supply)
and/or S0 counting value inputs
MVL 4/4
module with 24V DC, 5 mA inputs
(24V optional internal supply)
and/or S0 counting value inputs
and relay outputs normally open
max. 250V AC, 5A, 25V DC, 5A
MVL 0/8
module with relay outputs normally open
max. 250V AC, 5A, 25V DC, 5A
System features:
- Snap-on housing for distributor installation in snap-on breakers design 106 x 90 x 58mm high
- Degree of protection IP20
- Wide-range power supply with 85-265V AC / 85-250V DC or 18-50V AC / 19-72V DC, 100mA
- Connection: Screw-type terminals 2,5mm²
- Inputs 24V DC, 5mA or alternatively internal supplied with 24V and / or S0 counting value inputs (max. 17Hz)
- Available types:
MVL 8/0: 8x IN
MVL 4/4: 4x IN and 4x OUT (normally open)
MVL 0/8: 8x OUT (normally open) - Software and LNS 3.x PlugIn for lighting control, blind control, S0-counter capture
- EMC-values: UNITRO-Standard in accordance with EN 61000
Technical data:
- Type of construction:
snap-on housing
106 x 90 x 58mm high
- Degree of protection:
IP20
- Weight:
approx. 300g,
depending on equipment variant
- Climatic conditions:
in accordance with UNITRO-Standard
- Connection:
screw-type terminals max. 2,5mm²
- Function buttons:
reset button
service button
- Supply voltage:
24V AC/DC (=15-50V AC, 19-72V DC),
230V AC/DC (= 85-265V AC, 85-250V DC), 100mA
- Max. fuse:
4A medium slow
- Signal voltage:
24V DC ± 10%, 5mA or
alternatively internal supplied with 24V
- Response delay:
25ms
- Minimum signal duration:
5ms
- LED-display:
operating LED green
service LED yellow:
flashing = device not initialized
continuous light = error
TX LED yellow: bus activity device
RX LED yellow: bus utilization
for every input and output each 1x red LED
- Neuron chip:
3150, 10 MHz + 64kB Flash-EEPROM with FT-X transceiver
- Transmission:
LON FTT10A two wire (twisted-pair),
78kbps, max. 2,7km
- Bus connection:
isolated transceiver, 500V disconnecting insulation voltage
- Relay outputs:
isolated normally open: 250V AC, 5A / 25V DC, 5A
disconnecting voltage: 2000Vrmsinductive load (contactors):
mount-in anti-interferencecapacitors at the coils,
when driving roller shutter / blind motors, etc. by NO, is for an external interlock (up / down) to make!
- Leakage distances and clearances:
in accordance with UNITRO-Standard
- EMC, immunity of interference:
UNITRO-Standard,
in accordance with EN 61000
subject to change