TCP/IP SmartManager
Router für LONWORKS ® Powerline or Free-Topology Networks, for distributor installation
Type designation:
SmartManager
with the SmartManager can LONWORKS®
networks using TCP/IP (including DSL)
are interconnected.
SmartManager-GSM
with the SmartManager GSM can
LONWORKS® networks without landline
connection with a GSM mobile
route using TCP/IP are interconnected.
System features:
- The SmartManager connects LONWORKS® networks to the mobile Internet
- 10/100BaseT - Ethernet interface
- Remote network interface (RemoteCollector from Windows 7 Pro) as LONWORKS® interface
- Connection to LONWORKS® networks with Power line (PLT) or Free-Topology (FTT)
- Built coupling possible for the Power Line version
- Internet access is protected by standard security procedures
- Parameterization via standard browser
- Option: Quad-band UMTS module
- EMC-values: UNITRO-Standard in accordance with EN 61000
Technical data:
- Type of construction:
snap-on housing for DIN-Rail mounting
108 (+36 (LON)+34 (Modem))x 90 x 64 mm
- Degree of protection:
IP20
- Weight:
approx. 300g
- Climatic conditions:
temperature: 0-50 °C,
humidity: 0-90 % (not condensing)
- Connection:
screw-type terminals/ plug connection max. 2,5mm²
- Ethernet interface:
10/100 BaseT RJ45 interface
- USB interface:
for data logging via USB stick
- Supply voltage:
24V DC, max. 450mA ± 10-15%
120V bis 230V AC max. 60mA ± 10-15%
180V bis 360V DC max. 60mA ± 10-15%
- Processor:
32bit RISC-Processor,Neuron® 3150
- UMTS module:
Quad-band GSM-/Tri-band UMTS
Temperature range: -30° C to + 70° C
with slot for SIM card
- LED display:
LED yellow: GSM/GPRS module ready
LED green: power on
Service LED yellow:
flashing = device not initialized
continuous light = error
LED geen: PKD (packed detect)
lights up during data transmission
LED yellow: BIU (band in use)
lights at the reception or if occupied band
- Transmission:
LON-FTT: two wire (twisted-pair),
78kbps, max. 2,7kmLON-PLT: two wire (C-band 125-145kHz) 4,8kBit/s, max. 30km
in conjunction with phase coupler also power line transmission on the 230/400V AC
- Parameterization:
via standard browser
- Leakage distances and clearances:
in accordance with UNITRO-Standard
- EMC, immunity of interference:
UNITRO-Standard,
in accordance with EN 61000
subject to change
LONWORKS is a registered trademark of Echelon Corporation