Collection alarm indication units FSB 08/16-48 -SA
for front panel installation, 8 - 48 signal inputs
Type designation:
FSB 16/08 (16) -SA
collective alarm indicating unit
for 8 or 16 signal inputs,
with new-value horn alarm and LED-test
FSB 48/08 (16/24/32/40/48) -SA
collective alarm indicating unit
for 8 to 48 signal inputs in 8 input steps,
with new-value horn alarm and LED-test
Controls and displays
- Bright 5mm LED display
- Separate status indicator (green = Power ON)
- Easily exchangeable label strips
- Integrated small horn and function buttons
Parameterization
- With selector
- Quiescent / operating current, in groups of 8 (24-110V)
Electrical characteristics
- 8 - 48 signal inputs with LED-display red
- Continuous light during pending message
- No signal storage
- Integrated smal horn
- EMC-values: UNITRO-Standard in accordance with EN 61000
- Group alarm change-over contact max. 5A 250V AC, 3A 30V DC
Mechanical characteristics
- Compact plastic junction housing 96 / 192 x 96 x 85 + 25mm. Degree of protection: front IP50
- Connection: Screw-type terminals, plug connection max. 2,5mm²
Technical data:
- Type of construction:
control board housing
96 / 192 x 96 x 85 + 25mm
(cutting for installation: 92 / 186 x 92 + 1mm)
- Degree of protection:
front IP50, rear IP20
(front FSB 08/16 option IP54)
- Weight:
FSB 16 approx. 400g
FSB 48 approx. 650g
- Climatically conditions:
in accordance with UNITRO-Standard
- Connection:
screw-type terminals/ plug connectionmax. 2,5mm²
- Front panel buttons:
acknowledge horn
LED test
- External button:
acknowledge horn (normally open contact)
- Supply voltage:
24V AC/DC, 60V DC ± 10 - 15% or
230V AC ± 10 - 15% or
60 / 110 / 220V DC, ± 10 - 15%
voltage-adapted
- Max. fuse:
4A medium slow - Minimum signal duration:
DC: 10ms / AC:100ms
- Input level for signal inputs:
24V AC/DC ± 10% - 15% max. 7mA
230V AC ± 10% - 15% max. 2,9mA
for special applications with high power loss:
60V DC ± 10% - 15% max. 7mA
110V DC ± 10% - 15% max. 6mA
220V DC ± 10% - 15% max. 6mA
voltage-adapted
voltage tolerance ±10%
- Power loss 100% ED:
max. 2W + 8x 1,3W
attention: from 60V forced ventilation
power loss per signal:
60V DC 0,5W
110V DC 0,7W
220V DC 1,3W
- LED display:
labeled with marking strips
- alarm: red steady light
- no alarm: LED offpower on LED = green steady light
- Relay outputs:
1x group alarm and 1x horn contact,
potential-free change-over, max. 250V 5A
- Parameterization:
with selector switch, in groups of 8:
quiescence- / operation current (24-110V)
- Leakage distances and clearances:
in accordance with UNITRO-Standard
- EMC, immunity of interference:
UNITRO-Standard,
in accordance with EN 61000
subject to change