Collection alarm indication units FSB 08/16-48 -SA

for front panel installation, 8 - 48 signal inputs

Type designation:

FSB 16/08 (16) -SA
collective alarm indicating unit
for 8 or 16 signal inputs,
with new-value horn alarm and LED-test


FSB 48/08 (16/24/32/40/48) -SA
collective alarm indicating unit
for 8 to 48 signal inputs in 8 input steps,
with new-value horn alarm and LED-test

Controls and displays

  • Bright 5mm LED display
  • Separate status indicator (green = Power ON)
  • Easily exchangeable label strips
  • Integrated small horn and function buttons

Parameterization

  • With selector
  • Quiescent / operating current, in groups of 8 (24-110V)

Electrical characteristics

Mechanical characteristics

  • Compact plastic junction housing 96 / 192 x 96 x 85 + 25mm. Degree of protection: front IP50
  • Connection: Screw-type terminals, plug connection max. 2,5mm² 

Connection diagram FSB 16 and FSB 48-SA

Technical data:

  • Type of construction:
    control board housing

    96 / 192 x 96 x 85 + 25mm 
    (cutting for installation: 92 / 186 x 92 + 1mm)


  • Degree of protection:
    front IP50, rear IP20

    (front FSB 08/16 option IP54)


  • Weight:
    FSB 16 approx. 400g

    FSB 48 approx. 650g


  • Climatically conditions:
    in accordance with UNITRO-Standard


  • Connection:
    screw-type terminals/ plug connectionmax. 2,5mm²


  • Front panel buttons:
    acknowledge horn

    LED test


  • External button:
    acknowledge horn (normally open contact)


  • Supply voltage:
    24V AC/DC, 60V DC ± 10 - 15% or

    230V AC ± 10 - 15% or
    60 / 110 / 220V DC, ± 10 - 15% 
    voltage-adapted


  • Max. fuse:
    4A medium slow
  • Minimum signal duration:
    DC: 10ms / AC:100ms
  • Input level for signal inputs:
    24V AC/DC ± 10% - 15% max. 7mA

    230V AC ± 10% - 15% max. 2,9mA
    for special applications with high power loss:
    60V DC ± 10% - 15% max. 7mA
    110V DC ± 10% - 15% max. 6mA
    220V DC ± 10% - 15% max. 6mA
    voltage-adapted
    voltage tolerance ±10%


  • Power loss 100% ED:
    max. 2W + 8x 1,3W

    attention: from 60V forced ventilation
    power loss per signal:
    60V DC 0,5W
    110V DC 0,7W
    220V DC 1,3W


  • LED display:
    labeled with marking strips

    - alarm: red steady light
    - no alarm: LED off

    power on LED = green steady light


  • Relay outputs:
    1x group alarm and 1x horn contact, 

    potential-free change-over, max. 250V 5A


  • Parameterization:
    with selector switch, in groups of 8:

    quiescence- / operation current (24-110V) 


  • Leakage distances and clearances:
    in accordance with UNITRO-Standard


  • EMC, immunity of interference:
    UNITRO-Standard, 

    in accordance with EN 61000

subject to change