FSB 16-P USB - OUTR
flashing alarm annunciator units with signal storage
programmable via USB, for front panel installation, 16 signal inputs
Type designation:
FSB 16-P USB - OUTR
flashing alarm annunciator
16 signal inputs and relay output module,
outputs freely assignable for each signal
FSB 16: front panel installation
Controls and displays
- Bright 5mm LED display
- Status indicator (green = Power ON)
- Easily exchangeable label strips
- Integrated functional buttons
(+ external) + LED-Test
Parameterization
- via rear integrated Mini USB interface for parameterization each signal:
- quiescent / operating current,
- running- / alarm,
- assignment of the outputs
- response delay variable max. 10min,overall: new alert / first alert
Electrical characteristics
- 16 signal inputs with LED-display red
- Clocked input circuitry to reduce power loss
- Acknowledgeable flash warning
- Integrated mini horn
- EMC-values: UNITRO-Standard in accordance with EN 61000
- Input level for signal inputs and supply voltage:
48/60V DC, 110/125V DC, 220V DC
Mechanical characteristics
- Compact plastic junction housing
96 x 96 x 85 + 25mm, degree of protection: front IP50 - Connection: Screw-type terminals,
plug connection max. 2,5mm²
FSB 16-OUTR: snap-on module
Controls and displays
- LED display yellow (19x relay state),
illuminated when relay contacts are closed - LED yellow and red for internal data bus
(flashing yellow on intact data transfer,
continuous red light at fault) - Status indicator (green = Power ON)
Electrical characteristics
- 16 potential-free normally open, all poles led out relay contacts,
groupable on up to 2 contact groups with common root contact via integrated jumpers - 2x group alarm outputs change-over
with “device-disturbed" monitoring,
various settings are possible by means of programming software - 1x horn output change-over,
various settings are possible by means of programming software - EMC-values: UNITRO-Standard in accordance with EN 61000
- Relay contact rating:
24-250V AC, 2A / 110V DC, 0,5A / 220V DC, 0,3A
Mechanical characteristics
- Snap-on housing 200 x 100 x 60mm, degree of protection IP20
- Connection: Screw-type terminals,
plug connection max. 2,5mm²
Technical data:
- Type of construction:
FSB 16:
control board housing 96 x 96 x 85 + 25mm
(cutting for installation 92 x 92 + 1mm)
FSB 16-OUTR:
snap-on housing 200 x 100 x 60mm
- Degree of protection:
FSB 16: front IP50 (option IP54), rear IP20
FSB 16-OUTR snap-on housing IP20
- Weight:
FSB 16 approx. 400g
FSB 16-OUTR approx. 500g
- Climatically conditions:
in accordance with UNITRO-Standard
- Connection:
screw-type terminals/ plug connection max. 2,5 mm²
- Front panel buttons:
acknowledge horn
acknowledge flash light
LED test
- Supply voltage:
24V AC/DC or
48-60V AC/DC or
110/125V AC/DC or
220/240V AC/DC
voltage-adapted
- Max. fuse:
4A medium slow
- Input level for signal inputs:
48/60V DC -10% +15% max. 2,5mA
110/125V DC -10% +15% max. 2,5mA
220V DC -10% +15% max. 2mA
voltage-adapted
voltage tolerance ±10%
- Minimum signal duration:
DC: 10ms
- Data retention in the absence of power:
flash memory
- Power loss 100% ED:
60V DC max. 4,5W
110V DC / 220V DC max. 5,9W
- LED display:
FSB 16 control board housing, labeled with marking strips:
- alarm new alert: red flash light
- alarm acknowledge: red steady light
- alarm removed: LED dark
status LED (power on) = green steady lightFSB 16-OUTR snap-on housing:
- power on LED: green steady light
- data LED: yellow flash light
- data error LED: red steady light
- relay contact LED: yellow
- Flashing frequencies:
alarms 2Hz / 0,5Hz
- Relay outputs:
16 full potential-free normally open contacts,
the input messages about software as assigned
(assigned to Standard 1:1)
(reduced by jumpers on 4 common roots)2x group alarm messages and 1x horn contact,
potential-free change-over,
max. contact conditions-carrying capacity:
24-250V AC, 2A / 110V DC, 0,5A / 220V DC, 0,3A
- Parameterization:
via rear Mini USB interface
per input:
- running- / alarm
- quiescence- / operation current
- switch on delay max. 10min
- assignment of the output contactsoverall: first up / new alert
- Leakage distances and clearances:
in accordance with UNITRO-Standard
- EMC, immunity of interference:
UNITRO-Standard,
in accordance with EN 61000
subject to change