C3 digital IN + OUT
for DIN Rail mounting
Type designation:
C3 DI-8
8x potential-free digital inputs (24V)
for operation with C3 bus coupler
C3 DO-8
8x potential-free relay outputs normally open
max. 250V AC, 5A, 25V DC, 5A
for operation with C3 bus coupler
Controls and displays
- Bright LEDs for status display
- Dip-switch for the termination of the rail-bus
Parameterization of C 3 I/O modules via the C3 bus coupler
- Via Mini USB interface and software from Windows 7 Pro
- E.g. quiescent / operating current, delay time, etc.
Power supply
- Via DIN-rail-bus
Mechanical characteristics
- Compact Snap-on plastic housing (polyamide) 22,5 x 99 x 113,5mm with DIN-rail-bus
- Screw-type terminals, plug connection for connection max. 2,5mm²
Extensions
- Maximum total of 12x C3 I/O modules can be connected per bus coupler(from that max. 2x C3 ana GT)
Technical data:
- Type of construction:
snap-on plastic housing (polyamide)
with DIN-rail-bus 22,5 x 99 x 113,5mm
- Degree of protection:
IP20
- Weight:
approx. 150g
- Climatic conditions:
in accordance with UNITRO-Standard
- Connection:
screw-type terminals/ plug connection max. 2,5mm²
- Supply voltage:
via DIN-rail-bus
- Signal voltage:
24V DC ± 10%, 5mA per input
- Response delay:
25ms
- Minimum signal duration:
5ms
- LED-display:
see connection diagram
- Relay outputs:
normally open:
250V AC, 5A / 25V DC, 5A
electrical isolation: 2000Vrmsinductive load (contactors):
mount-in anti-interference capacitors at the coils,
please use external interlock, driving shutter or sun blind motors (up / down)!
- Parameterization:
via mini USB-interface on the Bus coupler,
connected with the DIN-rail-bus:
e.g. quiescent / operating current, delay time, etc.
- Leakage distances and clearances:
in accordance with UNITRO-Standard
- EMC, immunity of interference:
UNITRO-Standard,
in accordance with EN 61000
subject to change