Page 9 - LON-bus components
P. 9

Connection diagram MVE 8/8i


































            Technical data:
              1.   Type of construction:                   12.  LED-display:
                  snap-on housing                              operating LED green
                  100 x 75 x 45 (85)mm high                    service LED yellow: flashing =  device not initialized
              2.   Degree of protection:                                 continuous light  =  error
                  IP20                                         for every input and output each 1x red LED
              3.   Weight:                                13.  Neuron chip:
                  approx. 300g,                                3150, 10 MHz + 64kB Flash-EEPROM
                  depending on equipment variant          14.  Transmission:
              4.   Climatic conditions:                        LON FTT10A two wire (twisted-pair),
                  in accordance with UNITRO-Standard           78kbps, max. 2,7km
              5.   Connection:                            15.  Bus connection:
                  screw-type terminals/ plug connection        isolated transceiver, 500V disconnecting
                  max. 2,5mm²                                  insulation voltage
              6.   Function buttons:                      16.  Relay outputs:
                  reset button                                 isolated normally open:  250V AC, 5A / 25V DC, 5A
                  service button                               isolated change-over:   250V AC, 5A / 25V DC, 5A
                                                               disconnecting voltage:   2000Vrms
              7.   Supply voltage:
                  24V AC/DC, 100mA (± 10%),                    inductive load (contactors):
                  230V AC/DC (= 85-265V AC, 85-250V DC),       mount-in anti-interference capacitors at the coils,
                  100mA                                        when driving roller shutter / blind motors, etc. by NO, is for
                                                               an external interlock (up / down) to make!
              8.   Max. fuse:
                  4A medium slow                               option -H: with manual emergency switches
              9.   Signal voltage:                        17.  Leakage distances and clearances:
                  24V AC/DC ± 10%, 6mA                         in accordance with UNITRO-Standard
                  230V AC ± 10%, 6mA                      18.  EMC, immunity of interference:
              10.  Response delay:                             UNITRO-Standard,
                  25ms                                         in accordance with EN 61000
              11.  Minimum signal duration:
                  5ms

                                                      subject to change                                Page 108